60W DIN Rail Power Supply MDR-60

60W DIN Rail Power Supply MDR-60

Features:

  • Universal AC input/Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Built in DC OK active signal
  • LED indicator for power on
  • No load power consumption<0.75W
  • 100% full load burn-in test

Description

60W DIN Rail Power Supply MDR-60 Technical Data

MODELMDR-60-5MDR-60-12MDR-60-24MDR-60-48
OUTPUTDC VOLTAGE5V12V24V48V
RATED CURRENT10A5A2.5A1.25A
CURRENT RANGE0 ~ 10A0 ~ 5A0 ~2.5A0 ~ 1.25A
RATED POWER50W60W60W60W
RIPPLE & NOISE (max.) Note.280mVp-p120mVp-p150mVp-p200mVp-p
VOLTAGE ADJ. RANGE5 ~ 6V12 ~ 15V24 ~ 30V48 ~ 56V
VOLTAGE TOLERANCE Note.3±2.0%±1.0%±1.0%±1.0%
LINE REGULATION±1.0%±1.0%±1.0%±1.0%
LOAD REGULATION±15%±1.0%±1.0%±1.0%
SETUP, RISE TIME500ms, 30ms/230VAC     500ms, 30ms/115VAC at full load
HOLD TIME(Typ.)50ms/230VAC     20ms/115VAC at full load
INPUTVOLTAGE RANGE85 ~ 264VAC       120 ~ 370VDC
FREQUENCY RANGE47 ~ 63Hz
EFFICIENCY (Typ.)78%86%88%87%
AC CURRENT1.8A/115VAC     1A/230VAC
INRUSH CURRENT (max.)COLD START 30A/115VAC 60A/230VAC
PROTECTIONOVERLOAD105 ~ 150% rated output power
Protection type: Constant current limiting,recovers automatically after fault condition is removed
OVER VOLTAGE6.25 ~ 7.25V15.6 ~ 18V31.2 ~ 36V57.6 ~ 64.8V
Protection type: Shut down o/p voltage,re-power on to recover
FUNCTIONDC OK ACTIVE SIGNAL (max.)Relay contact rating(max.): 30V/1A resistive
ENVIRONMENTWORKING TEMP.-20 ~ +70ºC
WORKING HUMIDITY20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY-40 ~ +85ºC, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03%/ºC (0 ~ 50ºC)
VIBRATION10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC (Note 4)SAFETY STANDARDSDesign refer to UL508, TUV EN60950-1
WITHSTAND VOLTAGEI/P-O/P:3KVAC     I/P-FG:1.5KVAC     O/P-FG:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATIONCompliance to EN55022 (CISPR22) Class B
HARMONIC CURRENTCompliance to EN61000-3-2,-3
EMS IMMUNITYCompliance to EN61000-4-2,3,4,5; ENV50204, EN55024, Light industry level, criteria A
OTHERSMTBF229.2K hrs min.    MIL-HDBK-217F (25ºC  )
DIMENSION40*90*100mm (W*H*D)
PACKING0.33Kg; 42pcs/14.8Kg/0.82CUFT
NOTE1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.

60W DIN Rail Power Supply MDR-60 Mechanical

60W DIN Rail Power Supply MDR-60 Mechanical

60W DIN Rail Power Supply MDR-60 Certificate

LVD Certificate
EMC Certificate
RoHS Certificate

Send message