30W DIN Rail Power Supply DR-30

30W DIN Rail Power Supply DR-30

Features:

  • Universal AC input/Full range
  • Protections: Short circuit/Over load/Over voltage
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Isolation class Ⅱ
  • LED indicator for power on
  • 100% full load burn-in test

Description

30W DIN Rail Power Supply DR-30 Technical Data

MODELDR-30-5DR-30-12DR-30-15DR-30-24
OUTPUTDC VOLTAGE5V12V15V24V
RATED CURRENT3A2A2A1.5A
CURRENT RANGE0 ~ 3A0 ~ 2A0 ~ 2A0 ~ 1.5A
RATED POWER15W24W30W36W
RIPPLE & NOISE (max.) Note.280mVp-p120mVp-p120mVp-p150mVp-p
VOLTAGE ADJ. RANGE4.75 ~ 5.5V10.8 ~ 13.2V13.5 ~ 16.5V21.6 ~ 26.4V
VOLTAGE TOLERANCE Note.3±2.0%±1.0%±1.0%±1.0%
LINE REGULATION±1.0%±1.0%±1.0%±1.0%
LOAD REGULATION±1.0%±1.0%±1.0%±1.0%
SETUP, RISE TIME100ms, 30ms/230VAC     100ms, 30ms/115VAC at full load
HOLD TIME(Typ.)100ms/230VAC     30ms/115VAC at full load
INPUTVOLTAGE RANGE85 ~ 264VAC       120 ~ 370VDC
FREQUENCY RANGE47 ~ 63Hz
EFFICIENCY (Typ.)74%81%82%83%
AC CURRENT0.88A/115VAC     0.48A/230VAC
INRUSH CURRENT (max.)COLD START 15A/115VAC 30A/230VAC
PROTECTIONOVERLOAD105 ~ 160% rated output power
Protection type: Constant current limiting,recovers automatically after fault condition is removed
OVER VOLTAGE5.75 ~ 6.75V13.8 ~ 16.2V17.25 ~ 20.25V27.6 ~ 32.4V
Protection type: Shut down o/p voltage,re-power on to recover
ENVIRONMENTWORKING TEMP.-20 ~ +60ºC
WORKING HUMIDITY20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY-20 ~ +85ºC, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03%/ºC (0 ~ 50ºC)
VIBRATION10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC (Note 4)SAFETY STANDARDSDesign refer to UL60950-1, TUV EN60950-1,EN50178
WITHSTAND VOLTAGEI/P-O/P:3KVAC     I/P-FG:1.5KVAC     O/P-FG:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATIONCompliance to EN55022 (CISPR22) Class B
HARMONIC CURRENTCompliance to EN61000-3-2,-3
EMS IMMUNITYCompliance to EN61000-4-2,3,4,5; ENV50204, EN55024, Light industry level, criteria A
OTHERSMTBF441.5K hrs min. MIL-HDBK-217F (25ºC)
DIMENSION78*93*56mm (L*W*H)
PACKING0.27Kg; 48pcs/14Kg/1.02CUFT
NOTE1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

30W DIN Rail Power Supply DR-30 Mechanical

30W DIN Rail Power Supply DR-30 Mechanical

30W DIN Rail Power Supply DR-30 Certificate

LVD Certificate
EMC Certificate
RoHS Certificate

Send message