240W DIN Rail Power Supply DRP-240

240W DIN Rail Power Supply DRP-240

Features:

  • Universal AC input / Full range
  • Built in active PFC function
  • Protections: Short circuit/Over load/Over voltage/Over temperature
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • LED indicator for power on
  • 100% full load burn-in test
  • Fixed switching frequency at 100KHz

Description

240W DIN Rail Power Supply DRP-240 Technical Data

MODELDRP-240-24DRP-240-48
OUTPUTDC VOLTAGE24V48V
RATED CURRENT10A5A
CURRENT RANGE0 ~ 10A0 ~ 5A
RATED POWER240W240W
RIPPLE & NOISE (max.) Note.280mVp-p150mVp-p
VOLTAGE ADJ. RANGE24 ~ 28V48 ~ 53V
VOLTAGE TOLERANCE Note.3±1.0%±1.0%
LINE REGULATION±0.5%±0.5%
LOAD REGULATION±1.0%±1.0%
SETUP, RISE TIME800ms,40ms/230VAC   800ms, 40ms/115VAC at full load
HOLD TIME(Typ.)24ms/230VAC      24ms/115VAC at full load
INPUTVOLTAGE RANGE  Note.585 ~ 264VAC          120 ~ 370VDC
FREQUENCY RANGE47 ~ 63Hz
POWER FACTOR (Typ.)0.96/230VAC          0.99/115VAC at full load
EFFICIENCY (Typ.)84%85%
AC CURRENT2.8A/115VAC     1.4A/230VAC
INRUSH CURRENT (max.)COLD START 27A/115VAC 45A/230VAC
LEAKAGE CURRENT<3.5mA/240VAC
PROTECTIONOVERLOAD105 ~ 150% rated output power
Protection type: Constant current limiting,recovers automatically after fault condition is removed
OVER VOLTAGE30 ~ 36V54 ~ 60V
Protection type: Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE100ºC±5ºC (TSW1) Detect on heat sink of power transistor
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down
ENVIRONMENTWORKING TEMP.-10 ~ +70ºC
WORKING HUMIDITY20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY-20 ~ +85ºC, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03%/ºC (0 ~ 50ºC)
VIBRATION10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC (Note 4)SAFETY STANDARDSDesign refer to UL508, UL60950-1, TUV EN60950-1
WITHSTAND VOLTAGEI/P-O/P:3KVAC     I/P-FG:1.5KVAC     O/P-FG:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATIONCompliance to EN55011,EN55022 (CISPR22) Class B
HARMONIC CURRENTCompliance to EN61000-3-2,-3
EMS IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A
OTHERSMTBF136.8K hrs min. MIL-HDBK-217F (25ºC)
DIMENSION125.5*125.2*100mm (L*W*H)
PACKING1.2Kg; 12pcs/15.5Kg/1.2CUFT
NOTE1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
5.derating may be needed under lpw input voltages.Please check the derating curve for more details.

240W DIN Rail Power Supply DRP-240 Mechanical

240W DIN Rail Power Supply DRP-240 Certificate

LVD Certificate
EMC Certificate
240W DIN Rail Power Supply DRP-240 EMC Certificate
RoHS Certificate

Send message