100W DIN Rail Power Supply MDR-100

100W DIN Rail Power Supply MDR-100

Features:

  • Universal AC input/Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Built in DC OK active signal
  • LED indicator for power on
  • No load power consumption<0.75W
  • 100% full load burn-in test

Description

100W DIN Rail Power Supply MDR-100 Technical Data

MODELMDR-100-12MDR-100-24MDR-100-48
OUTPUTDC VOLTAGE12V24V48V
RATED CURRENT7.5A4A2A
CURRENT RANGE0 ~ 7.5A0 ~ 4A0 ~ 2A
RATED POWER90W96W96W
RIPPLE & NOISE (max.) Note.2120mVp-p150mVp-p200mVp-p
VOLTAGE ADJ. RANGE12 ~ 15V24 ~ 30V48 ~ 56V
VOLTAGE TOLERANCE Note.3±1.0%±1.0%±1.0%
LINE REGULATION±1.0%±1.0%±1.0%
LOAD REGULATION±1.0%±1.0%±1.0%
SETUP, RISE TIME3000ms, 50ms/230VAC 3000ms, 50ms/115VAC at full load
HOLD TIME(Typ.)50ms/230VAC     20ms/115VAC at full load
INPUTVOLTAGE RANGE85 ~ 264VAC       120 ~ 370VDC
FREQUENCY RANGE47 ~ 63Hz
EFFICIENCY (Typ.)83%86%87%
AC CURRENT1.3A/115VAC     0.8A/230VAC
INRUSH CURRENT (max.)COLD START 30A/115VAC 60A/230VAC
PROTECTIONOVERLOAD105 ~ 150% rated output power
Protection type: Constant current limiting,recovers automatically after fault condition is removed
OVER VOLTAGE15.6 ~ 18V31.2 ~ 36V57.6 ~ 64.8V
Protection type: Shut down o/p voltage,re-power on to recover
OVER TEMPERATUREShut down o/p voltage, auto-recovery or re-power on to recover
FUNCTIONDC OK ACTIVE SIGNAL (max.)Relay contact rating(max.): 30V/1A resistive
ENVIRONMENTWORKING TEMP.-10 ~ +60ºC
WORKING HUMIDITY20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY-40 ~ +85ºC, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03%/ºC (0 ~ 50ºC)
VIBRATIONComponent : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6
SAFETY & EMC (Note 4)SAFETY STANDARDSDesign refer to UL508, TUV EN60950-1
WITHSTAND VOLTAGEI/P-O/P:3KVAC     I/P-FG:2KVAC     O/P-FG:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMC EMISSIONCompliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
EMC IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
OTHERSMTBF346K hrs min. MIL-HDBK-217F (25ºC  )
DIMENSION55*90*100mm (W*H*D)
PACKING0.42Kg; 30pcs/13.6Kg/0.82CUFT
NOTE1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. Deating maybe needed under low input voltages, please check the dearating curve for more detail.